Safe-area load resistance 0 to 500鈩?/div>
Filter time constant
0 to 60s in 80ms increments
Relay type
Single-pole changeover relay
Relay characteristics
Switching voltage
<250V ac/120V dc
Switching current
<2A
Switching capacity
<500VA/60W
LED indicators
Green
Power
Yellow K1
Set point relay status
Yellow (Red)
Pulse indication (fault)
Power supply
230V ac nominal, 184鈥?64V ac, 48鈥?2Hz
(MTL5521-11-230)
115V ac nominal, 98鈥?26V ac, 48鈥?2Hz
(MTL5521-11-115)
24V dc nominal, 19鈥?9V dc, <10% ripple
(MTL5521-11-24)
Power consumption
<5VA/5W
Isolation
250V rms between input, output and power supply terminals,
tested at 2.5kV rms between safe and hazardous terminals
Terminals
Each terminal will accommodate 2x2.5mm
2
conductors
Mounting
On 35mm (top hat) rail
Location of units
Safe area
Ambient temperature limits
Operating temperature
鈥?0擄C to +60擄C
Dimensions
Height (above rail)
105mm
Width
89mm
Rail length required
36mm
Safety description
13V, 30mA (terminals 5鈥?)
U
m
= 250V ac
DIMENSIONS (mm)
13 14 15 16
9
36
10 11 12
Display
Pwr K1
S1
S2
89
5
1
6
2
7
3
8
4
110
EUROPE (EMEA)
Tel: +44 (0)1582 723633
Fax: +44 (0)1582 422283
AMERICAS
Tel: +1 603 926 0090
Fax: +1 603 926 1899
ASIA PACIFIC
Tel: +65 487 7887
Fax: +65 487 7997
E-mail: enquiry@mtl-inst.com
Web site: www.mtl-inst.com
June 2004