AS-i base
Dimensions
80
脴 9.6
26
36
18.5
18.5
36
26
脴 5.3
Model number
U-G1FA
Base with addressing jack for con-
nection to flat cable (EMS; AS-i only)
Technical data
General specifications
Addressing
Ambient conditions
Ambient temperature
Storage temperature
Mechanical specifications
Protection degree
Connection type
Dimensions
Mounting
via addressing jack
-25 ... 60 擄C (248 ... 333 K)
-25 ... 85 擄C (248 ... 358 K)
IP67 based on EN 60529
(only in connection with module or cover)
2 AS-i flat cables
about 80, 45, 20 mm (L, W, H)
top hat section rail or screw mounting
Function
The U-G1FA base allows slaves in the nor-
mal design to be connected to AS-i without
additional supply (EMS) . It has two connec-
tions to AS-Interface, which are intercon-
nected. Thus it can also be used as
distributor from one AS-i segment to
another. When mounting the upper part
(module or cover VAZ-DK-G1) the flat cable
are pressed in the contact prongs and the-
reby connected.
Moreover, an integrated addressing jack
can configure the upper part in the wired
AS-i network. In this case the controller indi-
cates 鈥濧larm Config鈥? since the slave is dis-
connected from the supply. After removing
the addressing plug, the controller restarts
independently.
Electrical connection
+
-
AS-i
AS-i
+
-
Addressing
jack
+
-
Contacts to module
45
Accessories
22.01.2002
Ausgabedatum
Accessories
VAZ-DK-G1
Cover for bases -G1F- and -G1P-
Subject to reasonable modifications due to technical advances.
Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group 鈥?Tel.: Germany (06 21) 7 76-0 鈥?USA (330) 4 25 35 55 鈥?Singapore 7 79 90 91 鈥?Internet http://www.pepperl-fuchs.com