Solid State Relays
SOLITRON
MINI
With Integrated Heatsink
鈥?AC Solid State Contactor
in 22.5 mm housing
鈥?Zero switching for heating and motor applications
鈥?Rated operational current 10 A and 20 A
鈥?Rated operational voltage 120/230 VAC, 400/480 VAC
and 600 VAC
鈥?Transient overvoltage protection
鈥?LED-indication
鈥?IP 20 protection
鈥?DIN-rail and backplate mountable
鈥?Terminal layout as contactor or SSR standard
鈥?Insulation > 4000 V
Product Description
The
SOLITRON
Mini Solid
State Contactor is designed
for industrial heating and
motor applications.
The Solid State Contactor is
designed for DIN-rail and
backplate mounting with inte-
grated heatsink and overvolt-
age protection. The heatsink
is moved to the back for opti-
mal space-saving in the panel
and easy wire mounting at
the front of the relay. The lim-
ited current rating limits the
need for optimal convection
cooling as provided with
Solitron 30, 50 and 63 A ver-
sions.
The contactor elements are
integrated on to the ceramic
providing more than 4000 V
insulation to the heatsink.
AC or DC controlled versions
are available with terminal
layout as the standard for
contactors or the US Mil-
standard for Solid State
Relays. Built-in LED status
indication for applied control
voltage.
Ordering Key
Solid State Relay
Number of poles
Switching type
Rated operational voltage
Control voltage
Rated operational current
Terminal layout
RN 1 A 48 D 20 E
Type Selection
Rated
operational
voltage
120/230 VAC
400/480 VAC
600 VAC
Control
voltage
Rated operational current:
Contactor terminal layout
AC1: 10 A
AC1: 20 A
AC3: 3 A
AC3: 5 A
RN 1A23D10E
RN 1A23A10E
RN 1A48D10E
RN 1A48A10E
RN 1A60D10E
RN 1A60A10E
RN 1A23D20E
RN 1A23A20E
RN 1A48D20E
RN 1A48A20E
RN 1A60D20E
RN 1A60A20E
Standard SSR terminal layout
AC1: 10 A
AC1: 20 A
AC3: 3 A
AC3: 5 A
RN 1A23D10U
RN 1A23A10U
RN 1A48D10U
RN 1A48A10U
RN 1A60D10U
RN 1A60A10U
RN 1A23D20U
RN 1A23A20U
RN 1A48D20U
RN 1A48A20U
RN 1A60D20U
RN 1A60A20U
5-32 VDC
24-265 VAC/DC
5-32 VDC
24-265 VAC/DC
5-32 VDC
24-265 VAC/DC
General Specifications
RN1A23....
Operational voltage range
Non-rep. peak voltage
Varistor voltage
Operational frequency range
Power factor at rated voltage
CE-marking
(External filter for EN 50081-1 needed.)
RN1A48....
42 to 530 VAC
1200 V
p
510 VAC
45 to 65 Hz
鈮?/div>
0.5
Yes
RN1A60....
42 to 660 VAC
1400 V
p
625 VAC
45 to 65 Hz
鈮?/div>
0.5
Yes
42 to 265 VAC
600 V
p
275 VAC
45 to 65 Hz
鈮?/div>
0.5
Yes
Norms fulfilled
IEC 60158-2
EN 50082-2
Semiconductor Contactors
Generic Immunity Standard, Industrial Environment
Specifications are subject to change without notice (30.06.1999)