AXIAL LEAD AND CARTRIDGE FUSES
DESIGNED TO IEC STANDARD
5 x 20 mm
Fast-Acting Type
鈥?Designed to International (IEC) Standards for use globally.
鈥?Meets the IEC 127-2, Sheet 1 specification for Fast Acting
Fuses.
鈥?Available in Cartridge and Axial Lead Form.
鈥?Available in ratings of 0.050 to 10 amperes.
ELECTRICAL CHARACTERISTICS:
% of Ampere
Rating
150%
210%
275%
400%
1000%
Ampere
Rating
.05 鈥?3.15
4鈥?6.3
.05 鈥?3.15
4鈥?6.3
.05 鈥?3.15
4鈥?6.3
.05 鈥?3.15
4鈥?6.3
.05 鈥?3.15
4鈥?6.3
Opening
Time
60 minutes,
Minimum
60 minutes,
Minimum
30 minutes,
Maximum
30 minutes,
Maximum
0.01 sec.,
Min.;
2 sec.
Max.
0.01 sec.,
Min.;
3 sec.
Max.
.003 sec.,
Min.;
0.3 sec.
Max.
.003 sec.,
Min.;
0.3 sec.
Max.
.02 seconds,
Maximum
.02 seconds,
Maximum
廬
廬
D
V
E
216
000
Series
226
000
Series
.635
(.025")
5
(.197")
20
(.787")
5.25
(.207")
20.24
(.797")
40
(1.58")
AGENCY APPROVALS: Sheet I
IEC 127-2:* SEMKO
approved thru 6.3 amps. Recognized under the
Components Program of Underwriters Laboratories and
recognized by CSA.KEMA approved to 6.3A. BSI approved
1A to 6.3A. VDE approved .05鈥?2, .315鈥?.3.
INTERRUPTING RATING:
1500 amperes.
ORDERING INFORMATION:
Cartridge
Catalog
Number
216.050
216.063
216.080
216.100
216.125
216.160
216.200
216.250
216.315
216.400
216.500
216.630
216.800
216
001
216
1.25
216
01.6
216
002
216
02.5
216
3.15
216
004
216
005
216
06.3
216
008
216
010
Axial Lead
Catalog
Ampere Voltage
Number
Rating Rating
226.050
.050
250
226.063
.063
250
226.080
.080
250
226.100
.100
250
226.125
.125
250
226.160
.160
250
226.200
.200
250
226.250
.250
250
226.315
.315
250
226.400
.400
250
226.500
.500
250
226.630
.630
250
226.800
.800
250
226
001
1
250
226
1.25
1.25
250
226
01.6
1.6
250
226
002
2
250
226
02.5
2.5
250
226
3.15
3.15
250
226
004
4
250
226
005
5
250
226
06.3
6.3
250
226
008
8*
250
226
010
10*
250
Nominal
Resistance
Cold Ohms
15.90
10.45
7.89
5.42
3.68
5.20
3.35
2.35
1.85
1.67
1.20
0.790
0.588
0.228
0.153
0.108
0.0770
0.0575
0.0333
0.0243
0.0168
0.0125
0.0120
0.00775
Nominal
Melting I
2
t
A
2
Sec.
0.00019
0.00055
0.00086
0.0033
0.0056
0.0018
0.0045
0.0092
0.015
0.028
0.045
0.097
0.18
0.19
0.49
1.04
1.92
2.77
7.85
15.4
28.2
57.9
66.1
158.5
Average Time Current Curves
.100A
.125A
.160A
.200A
.250A
.315A
.500A
.630A
.800A
1A
1.25A
1.6A
2A
2.5A
3.15A
4A
5A
6.3A
10A
1
10
CURRENT IN AMPERES
100
10
TIME IN SECONDS
1
0.1
0.01
0.001
0.05 0.1
100
500
*IEC Standards for 5 x 20mm fuses do not include ratings above
6.3 amperes.